RussianPatents.com

Method for locating single-phase ground fault in three-phase power transmission line

Method for locating single-phase ground fault in three-phase power transmission line
IPC classes for russian patent Method for locating single-phase ground fault in three-phase power transmission line (RU 2244941):
G01R31/08 - Locating faults in cables, transmission lines, or networks (emergency protective circuit arrangements H02H)
Another patents in same IPC classes:
Method for locating single-phase ground fault in three-phase power transmission line Method for locating single-phase ground fault in three-phase power transmission line / 2244941
Proposed method involves detection of first failed phase on occurrence of single-phase ground fault, disconnection of power-transmission line from power supply, shorting-out of first failed phase and conductor of second serviceable phase at certain distance in end of power transmission line, grounding of neutral point of power supply or lead of one of its serviceable phases, connection of power transmission line to power supply, and measurement of emergency parameters. Chosen out of emergency parameters are current through first failed phase, current through second serviceable phase, and phase angles of these currents relative to voltage between mentioned first and second phases. Distance to point of single-phase ground fault is found from expression interrelating mentioned parameters.
Device for detecting single-phase ground faults in insulated-neutral networks Device for detecting single-phase ground faults in insulated-neutral networks / 2244992
Proposed device designed for detecting faulty outgoing line of 6- 10 kV insulated-neutral network on occurrence of single-phase ground fault in this network makes it possible to tune away from aperiodic component of singe-phase ground fault process, to eliminate malfunction during damped oscillations of zero-sequence current and voltage signals, and to save information about faulty line number. Device also provides for resetting zero-sequence current and voltage phase comparison element in preset time upon elimination of single-phase ground fault.
Short circuit current flow indicator Short circuit current flow indicator / 2248001
Indicator can be used for finding damaged parts in distribution network at short circuit breakdown. Indicator is installed in distribution and transformer stations and has plate made of material having paramagnetic, diamagnetic or ferromagnetic properties, vertical axis of rotation and horizontal arm. Top and lower ends of plate are bent to one side at angle of 90 deg and have several pairs of holes disposed symmetrically to adjust torque. Plate is mounted with selected pair of holes onto vertical axis of rotation which has lower end fixed to horizontal arm. Arm is attached to vertical member of bus.
Method for location of single-phase ground fault in branched aerial power line with insulated neutral conductor Method for location of single-phase ground fault in branched aerial power line with insulated neutral conductor / 2248583
The method provides for fixation of an emergency signal, then the electric and magnetic field strengths are measured as an emergency signal in succession in the point of branching and under each branch of the aerial power line, converted to harmonic components of the voltage and current signals proportional to them, with the aid of the Fourier transform for each harmonic the amplitude and the phase angles of the harmonic components of the voltage and current signals are determined, from the sequence of the values of the amplitudes of harmonic components of the voltage and current signals the i-th harmonic component with the maximum amplitudes of harmonic components of the voltage and current signals is separated, comparing them with the proportional maximum allowable amplitudes measured in the normal operating conditions of the power line, and according to the excess of the values of the amplitudes of the components of the voltage and current components of the separated i-th harmonic, the branch with a faulty condition, the direction to the point of the ground fault in it are determined according to the sign of the shift between the harmonic components of the voltage and current signals of the separated i-th harmonic, for the positive sign of the phase shift angle between the harmonic components of the voltage and current signals the direction of search "to the right" corresponds, and for the negative sign of the phase shift angle between the harmonic components of the voltage and current signals the direction of search "to the left" corresponds, the point of ground fault in this branch is determined according to the change of the sign of the phase angle shift between the harmonic components of the voltage and current signals of the separated i-th harmonic, measuring the strengths of the electric and magnetic fields, moving under the aerial power line along the faulty branch.
Method of measuring remoteness of single-phase short circuit in three-phase power line Method of measuring remoteness of single-phase short circuit in three-phase power line / 2249226
First phase with damage insulation is found and power line is switched off of three-phase power line. Second and third phases with non-damaged insulation are closed to ground by means of jumpers at beginning and end of power line at known distance from start point of power line. Single-phase ac source is removed from beginning of power line between first phase with damaged insulation and ground. Voltage between first phase with damaged insulation and ground at beginning of power line is measured, then current is measured in first phase as well as phase angle between the voltages and current. After it distance to single-phase short-circuit is determined.
Method of measuring distance to point of single-phase short circuit onto ground in radial distribution circuits Method of measuring distance to point of single-phase short circuit onto ground in radial distribution circuits / 2250472
Method concludes in registering voltage of damaged phase at buses of power supply in digital form and subsequent analyzing that voltage. Voltage to be measured is standardized from the moment of beginning of short-circuit in relation to breakdown voltage and sums of standard deviations
Method of detecting defects in tightness of electric insulation / 2250473
Method can be used for inspection of integrity of electric insulation. According to the method item is placed into transparent chamber filled with special liquid and is subject to physical action. Tightness of item is judged from bubbles of gas. Physical action concludes in applying physical load during 10-600 seconds and electrical load is set within range of 500-2500 V. Transformer oil is used as technical oil with water content of 0,01-0,1%.
Method of finding feeder with single-phase arc fault to ground in radial distribution cable circuits Method of finding feeder with single-phase arc fault to ground in radial distribution cable circuits / 2254586
Method can be used for finding feeder with single-phase arc fault to ground in radial distribution cable circuits of 6-10 kV having isolated and resonant-compensated neutral conductor or with neutral conductor earthed through high-ohmic resistor. Transient voltages at buses of main point are registered in single-phase shorting as well as first half-waves of transient currents in feeders coming from the buses. Polarities of currents are juxtaposed. Feeder having current polarity being opposite to the others is supposed to be damaged. In this case shorting mode is recognized on the base of analysis of phase voltages at buses of main supply point. After that the polarities of first half-waves of transient currents being registered in conductors connecting envelopes of cables with grounding mat have to be compared.
Method of measuring distance to single-phase short circuit to ground in electric circuit Method of measuring distance to single-phase short circuit to ground in electric circuit / 2258233
Device can be used for remote measurement of distance till site of damage - steady single-phase to ground, for example, at melting ice on ground by alternative or direct current. Method is based on measurement and storage of value of current, which passes through grounding electrode. The electrode is connected in turn at least two times to different points of circuit at the side of power line where it was short circuited onto ground. Distance to place of short circuit is subsequently calculated from the values and known parameters of electric circuit. Error in measurement of distance is reduced at big transient resistance due to rejection of usage of parameters of higher frequency mode.
Device for determining the place of one-phase ground in the networks with insulated neutral Device for determining the place of one-phase ground in the networks with insulated neutral / 2260812
Proposed device is related to ensuring the normal functioning of the railroad high-voltage lines of longitudinal electric power supply with insulated neutral. A current transducers is switched into one from undamaged phases, closed with the damaged phase on the near end of line. The switch is located on the far end of line and has possibility closing and breaking of the undamaged and damaged phases with the current transducer. The measuring part is carried out with successively switched arithmetical device, functional corrector and indicator. The device has also a stabilized constant-current source, intended for supplying two measuring circuits by the current of equal value. The constant-current source is switched between the ground and phases, closed on the near end of line. This measuring part has also a control device and voltmeter with parallel connection to the stabilized constant-current source. The control device ensures possibility to control the voltmeter operation for realization of the peaking-difference function of this voltmeter in the modes with broken and closed switch. Besides the control device has possibility to control the arithmetical device, obtaining the information from the voltmeter on fulfillment the subtraction function of voltage, obtained in the second mode, from the first mode voltage, loaded preliminary into memory. The arithmetic device has possibility to realize the division of obtained voltage difference by the current, measured with current transducer, and to transmit the division result into the functional corrector. The last has possibility to take into account the line parameters and to convert the division result into a signal, convenient for readout on the indicator of information about the distance from substation up to the place of phase ground.

FIELD: instrumentation engineering; three-phase single-ended insulated- or compensated-neutral supply mains.

SUBSTANCE: proposed method involves detection of first failed phase on occurrence of single-phase ground fault, disconnection of power-transmission line from power supply, shorting-out of first failed phase and conductor of second serviceable phase at certain distance in end of power transmission line, grounding of neutral point of power supply or lead of one of its serviceable phases, connection of power transmission line to power supply, and measurement of emergency parameters. Chosen out of emergency parameters are current through first failed phase, current through second serviceable phase, and phase angles of these currents relative to voltage between mentioned first and second phases. Distance to point of single-phase ground fault is found from expression interrelating mentioned parameters.

EFFECT: enhanced measurement accuracy, facilitated location of single-phase ground fault.

1 cl, 1 dwg

 

The invention relates to electric networks, namely a three-phase transmission lines with isolated or compensated neutral and unilateral power, and can be used, for example, to determine the distance of a single-phase earth fault in three-phase power lines for power supply Autolock on electrified Railways.

Especially the performance and operation of high voltage transmission lines for power supply Autolock on the Railways is described in [1]. These three-phase transmission lines are isolated in the case of unilateral power.

The first feature of the three-phase power lines for power supply Autolock Railways compared with three-phase power lines other purpose is the fact that for 20-40 km to its wires at intervals of 1-3 km connect single-phase load. Each connection point is attached to only one load. For balancing the transmission line load at different locations connected to different phases. However, including due to the different power loads and their changes over time, complete symmetry is not achieved. Download a different phase of such a transmission line may differ by 10-30 percent, which is many times revised the asymmetry of the three-phase power lines for other purposes.

The second feature are small differences in the values of current remote short circuit of the load current. So, under normal load phases 4-6 and wires type PSO-5 current deaf short circuit due to damage at the end of the transmission line is 6-10 And, if the closure occurs through transient resistance, and even less [1].

The third feature is that when the remote closures, as long transmission lines and small values of the currents) currents transverse capacitive conductivity between the phase with damaged insulation and phase with intact insulation to be commensurable with the short circuit current.

The fourth feature is that on electrified Railways single-phase AC power line to supply the Autolock is close to the contact network. Single-phase contact network brings all the wires of this line is approximately the same voltage due to electromagnetic effects. This effect is significantly greater than from any other three-phase transmission line.

These features can significantly affect the accuracy of determining the distance of a single-phase earth fault on the parameters of the emergency mode. It is known that in a network with isolated neutral parameters ABAP is logo mode when the circuit of one phase to ground (phase or line voltages and currents at the beginning of the line) do not have any information about the remoteness of damage. Therefore, the measurement of the parameters of the emergency mode with a three-phase transmission line with single-phase ground fault is switched to the mode of the single-phase short circuit by connecting the zero point of the supply transformer with the ground or in the mode of two-phase short circuit to earth by connecting with earth a different phase with intact insulation.

The essence of the proposed method is illustrated by a drawing.

There is a method of determining the distance of the fault location isolation of a single phase transmission line by a ground fault zero point of the transformer supplying the three-phase power supply line for power supply Autolock, measurement of the phase voltage U1and current I1wires with damaged insulation and calculate the parameter Z1according to the formula

on the basis of which to judge the distance of the fault location isolation [1, p 121-122].

Also known variant of this method of determining the distance of the fault location isolation by earth fault not the zero point, and the other phase with intact insulation, measurement of the line voltage U12between these phases and the current I1wires with damaged insulation and calculate the parameter Z12by the formula

on the basis of which the judge about the remoteness of the insulation [2].

Both variants of this method have one major drawback, namely, that when shorted to ground through a large contact resistance proportionality between the parameter Z1or Z12and the distance to the fault disappears, the error in determining the distance of the damage becomes very large and does not provide the required accuracy and reliability of measurements [1, p.123].

There is a method of determining the distance of the fault location isolation of a single phase transmission line with grounded neutral by measuring the voltage U, current I and the phase angle ϕ between them and the calculation of the parameter N by the formula

on the basis of which the judge about the remoteness of damage to insulation, and as the voltage of the U phase voltage is used, and as the current I value I=If+C03I0where If- phase current wires with damaged insulation, Iabout- current zero-sequence. To0- compensation coefficient current zero-sequence [3, 6-8.].

The error in the determination of remoteness of damage in the presence of contact resistance in this way, compared with the previous reduced. However, the error is C-unbalanced, unevenly connected loads, currents transverse capacitive and inductive conductivity of a contact network influence remains quite large.

The known method 1 determine the distance of the place single-phase circuit three-phase transmission lines with isolated or compensated neutral and unilateral power by determining the phase with damaged insulation, grounding to the ground zero point or one of the intact phases of the power source and measurement parameters emergency mode, in which the following sequence of operations [4]:

1) define the first phase transmission lines with damaged insulation shutting on the ground, in a known manner by means of three voltmeters connected to the voltage transformer [1, s];

2) disconnect the power line from the power source in a known manner by means of a three-phase circuit breaker;

3) perimysium between a short-circuited wire of the first phase with damaged insulation and the second phase with intact insulation at the end of the transmission line at a certain distance from the power source with a jumper;

4) unlock the feeding end of the third phase with intact insulation using, for example, a switching device;

5) connect the earth wire of the third phase with intact and what Alecia at the beginning and end of the transmission line jumpers;

6) is connected to the ground zero point or the output M of the second phase with intact insulation power source through a switching device, and the point M can be located either on the right or left of the switch;

7) connect the first phase with damaged insulation and the second phase with intact insulation of the transmission line to the power supply using the switch;

8) measure the voltage at the terminals of the power source between the first phase with damaged insulation and a second phase with intact insulation, as well as the value of the currents of the wires of these phases, using current transformers and voltage transformer;

9) determine the distance to a single-phase earth fault by the formula

where U12the voltage at the terminals of the power source between the first phase with damaged insulation and a second phase with intact insulation;

I1-current of the first phase with damaged insulation;

I2the current second phase with intact insulation;

z - resistivity direct sequence 1 km of three-phase transmission line;

L is the distance from the power source to the opposite end of the line.

The disadvantages of this method are:

1) the complexity of the implementation and the complexity of the algorithm. The complexity of implementing zaklyuche which are necessary to install three jumper and converted a three-phase separator (10, 11, 12 figure 1 of the patent [4]), since the known method 1 assumes that each phase of the disconnector has an individual drive and can be opened or closed regardless of the position of the disconnector in other phases (phase control). At the same time, the high-voltage disconnectors transmission line for power supply Autolock equipped with a standard three-phase disconnectors, all the phases of which are controlled by one actuator and can be either all on or all off [1]. The industry produces three-phase circuit breakers for a voltage of 6-10 kV (this voltage is applied in the above-mentioned transmission lines) with phase control.

2) the complexity of the algorithm is that in the numerator and the denominator requires operations with vector quantities.

In the proposed invention is applied typical three-phase disconnector, the third phase transmission lines with intact insulation separately from the other two phases is not turned off, instead of the three used only one jumper, see formula (algorithm) to calculate the distance to the fault takes into account all peculiarities of the electric circuit, is obvious and new, provides high accuracy.

The technical result is to increase accuracy and simplify the definition of the remoteness of defesnive earth fault.

The invention consists in that for determining the distance of the place of single-phase ground fault three phase transmission lines with isolated or compensated neutral one-way powered by determining the phase with damaged insulation, earth fault zero point or one of the intact phases of the power source, shorting at the end of the line short-circuited wires faulted phase and the second of the intact phases and measurement of parameters of the emergency mode, when a single-phase earth fault define the first phase with damaged insulation, turn off the power line from the power source at a known distance at the end of the transmission line perimysium between a short-circuited wire of the first phase with damaged insulation and the wire of the second phase with intact insulation, connected to the ground zero point or the conclusion of the third phase of the power source, connect the power line to the power supply, measure the current of the first phase with damaged insulation, the current second phase with intact insulation and phase angles of these currents relative to the voltage between the said first and second phases of the transmission line, and determine the distance to a single-phase earth fault by the formula:

where lk- be the tion from the supply end to place single-phase short circuit;

L is the distance from the power source to the opposite end of the line;

I1module current of the first phase with damaged insulation;

ϕ1is the phase angle of the current I1relative voltage between the first and second phases;

I2module current second phase with intact insulation;

ϕ2is the phase angle of the current I2with respect to the same voltage;

α - the argument is dependent on the design parameters of a transmission line.

The invention is illustrated in the drawing, where the following notation:

1 - wire of the first phase with damaged insulation of the transmission line;

2, 3 - wire, respectively, the second and third phase with intact insulation of the same transmission line;

4 - power;

5 - three-phase circuit breaker;

6 - three-phase disconnector;

7 - switching device;

8, 9, 10 - transformers;

11 - voltage transformer;

12 - jumper (zahratka).

When shorted to ground at a point To the wires of the first phase with damaged insulation perform the following operations:

1) define the first phase transmission lines with damaged insulation shutting on the ground, in a known manner by means of three voltmeters connected to the voltage transformer [1, s];

2) disable the line e is peredachi from the power source 4 in a known manner by using a three-phase switch 5 and switch 6;

3) perimysium between a short-circuited wire of the first phase 1 with damaged insulation and the second phase 2 with intact insulation at the end of the transmission line at a known distance L from the power source 4 with a jumper 12;

4) is connected to the ground zero point of the power source 4 or (shown dotted) output M of the third phase with intact insulation of this source using a switching device 7, and the point M can be located on both the left and right of the disconnector 6;

5) include the switch 6 and the switch 5;

6) measure the current of the first phase with damaged insulation, the current second phase with intact insulation and phase angles of these currents relative to the voltage between the said first and second phases of a transmission line using a measuring current transformers 9,10 and voltage 11;

7) determine the distance to a single-phase circuit using the above formula.

Operations 1, 2, 4, 5, operation 3, 6, and 7 are new.

The positive effect is due to two interrelated factors: the simultaneous exclusion of operations (a) - disconnection of the supply end of the third phase with intact insulation and the installation of two grounding jumpers in this phase at the beginning and end of the line and b) use a different formula (alternative algorithm for computing removed the barb damage). The destruction of the prototype of such essential characteristics as “unlock the feeding end of the third phase with intact insulation and connect it to the ground near the power source and at the opposite end of the transmission line leads to the necessity to use a new significant feature - mentioned formula to determine the distance of the damage. When this new type of formula (algorithm) is not obvious and is new.

The proposed method and the formula (algorithm) determine the distance of the place of single-phase earth fault completely rebuilt (insensitive) from electromagnetic influence of the contact network and the transition resistance at the injury site. As is known, these two factors cause the largest error in determining the distance of the fault location in transmission lines for power supply Autolock, reaching 100 percent or more. The proposed method for these factors does not respond, what ensures its high accuracy.

The possibility of carrying out the invention is ensured by the fact that the method operates well-known technical means without their reconstruction in comparison with typical designs (switch, circuit breaker, switching device, the current transformers and voltage, wire line, the power sources in the form of the transform is ora). The proposed formula (algorithm) contains only simple operations of elementary mathematics, easy to implement modern microprocessors.

Theoretical justification of the formula (algorithm) given in the Appendix.

Sources of information

1. Herman L.A., Veksler M.I., Solomon I.A. Device and the supply line Autolock. M: Transport; 1987. 192 C.

2. Figurov H.E., Taptykov E.G. the Definition of the remoteness of the circuits in high-voltage lines Autolock. In kN. Relay protection and automation devices supply rail. Interuniversity collection of works. Rostov Institute of engineers W-d transport, VIP. Rostov-on-don, RIIIT, 1978, s-86.

3. Eisenfeld A.I., Aronson, VN, The głowacki VG Locking indicator of the resistance of the FIS. M.: Energoatomizdat. 1987. 64 C.

4. Patent RU 2186404. Methods and apparatus for determining the distance of a single-phase circuit three-phase transmission line (options). /Appguru, Associ, Pastrav. CL. 7 G 01 R 31/08. No. 2001109805/09. Appl. 11.04.2001, publ. 27.07.2002, bull. No. 24.

The method of determining the distance of the place of single-phase ground fault in a three-phase transmission lines with isolated or compensated neutral one-way powered by determining if the occurrence of single-phase earth fault in the first phase with handicapped the insulation, disconnect the transmission line from the power source, shorting between a short-circuited wire of the first phase with damaged insulation and wires of the second phase with intact insulation on a known distance at the end of the transmission line, connected to the ground zero point of the power source or the output of one of its phases with intact insulation, connect the transmission line to the power source and measurement parameters emergency mode, characterized in that as the intact phase, connected to the earth, choose the third phase with intact insulation, and of the parameters of the emergency operation measure the current of the first phase with damaged insulation, the current second phase with intact insulation and phase angles of these currents relative to the voltage between the said first and second phases of the transmission line, the distance to the place of single-phase ground fault is determined by the expression

where lto- the distance from the feeding end to the place single-phase circuit,

L is the distance from the power source to the opposite end of the line,

I1module current of the first phase with damaged insulation,

ϕ1is the phase angle of the current I1relative voltage between the first and second phases,

I2module is Oka second phase with intact insulation,

ϕ2is the phase angle of the current I2with respect to the same voltage,

α - the argument is dependent on the design parameters of a transmission line.

 

© 2013-2014 Russian business network RussianPatents.com - Special Russian commercial information project for world wide. Foreign filing in English.